Power contactor, AC-3e/AC-3, 12 A, 5.5 kW / 400 V, 3-pole, 208 V AC, 50/60 Hz, auxiliary contacts: 1 NO, screw terminal, size: S00 | |||||
Product brand name | SIRIUS | ||||
Product designation | Power contactor | ||||
Product type designation | 3RT2 | ||||
General technical data | |||||
Size of contactor | S00 | ||||
Product extension | |||||
● function module for communication | No | ||||
● auxiliary switch | Yes | ||||
Power loss [W] for rated value of the current | |||||
● at AC in hot operating state | 1.5 W | ||||
● at AC in hot operating state per pole | 0.5 W | ||||
● without load current share typical | 1.5 W | ||||
Type of calculation of power loss depending on pole | Quadratic | ||||
Insulation voltage | |||||
● of main circuit with degree of pollution 3 rated value | 690 V | ||||
● of auxiliary circuit with degree of pollution 3 rated value | 690 V | ||||
Surge voltage resistance | |||||
● of main circuit rated value | 6 kV | ||||
● of auxiliary circuit rated value | 6 kV | ||||
Maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1 | 400 V | ||||
Shock resistance at rectangular impulse | |||||
● at AC | 7,3g / 5 ms, 4,7g / 10 ms | ||||
Shock resistance with sine pulse | |||||
● at AC | 11,4g / 5 ms, 7,3g / 10 ms | ||||
Mechanical service life (operating cycles) | |||||
● of contactor typical | 30 000 000 | ||||
● of the contactor with added electronically optimized auxiliary switch block typical | 5 000 000 | ||||
● of the contactor with added auxiliary switch block typical | 10 000 000 | ||||
Reference code according to IEC 81346-2 | Q | ||||
Substance Prohibitance (Date) | 10/01/2009 | ||||
Ambient conditions | |||||
Installation altitude at height above sea level maximum | 2 000 m | ||||
Ambient temperature | |||||
● during operation | -25 … +60 °C | ||||
● during storage | -55 … +80 °C | ||||
Relative humidity minimum | 10 % | ||||
Relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95 % | ||||
Environmental footprint | |||||
Environmental Product Declaration(EPD) | Yes | ||||
Global Warming Potential [CO2 eq] total | 39.6 kg | ||||
Global Warming Potential [CO2 eq] during manufacturing | 1.18 kg | ||||
Global Warming Potential [CO2 eq] during operation | 38.5 kg | ||||
Global Warming Potential [CO2 eq] after end of life | -0.155 kg | ||||
Main circuit | |||||
Number of poles for main current circuit | 3 | ||||
Number of NO contacts for main contacts | 3 | ||||
Operating voltage | |||||
● at AC-3 rated value maximum | 690 V | ||||
● at AC-3e rated value maximum | 690 V | ||||
Operational current | |||||
● at AC-1 at 400 V at ambient temperature 40 °C rated value | 22 A | ||||
● at AC-1 | |||||
— up to 690 V at ambient temperature 40 °C rated value | 22 A | ||||
— up to 690 V at ambient temperature 60 °C rated value | 20 A | ||||
● at AC-3 | |||||
— at 400 V rated value | 12 A | ||||
— at 500 V rated value | 9.2 A | ||||
— at 690 V rated value | 6.7 A | ||||
● at AC-3e | |||||
— at 400 V rated value | 12 A | ||||
— at 500 V rated value | 9.2 A | ||||
— at 690 V rated value | 6.7 A | ||||
● at AC-4 at 400 V rated value | 8.5 A | ||||
● at AC-5a up to 690 V rated value | 19.4 A | ||||
● at AC-5b up to 400 V rated value | 9.9 A | ||||
● at AC-6a | |||||
— up to 230 V for current peak value n=20 rated value | 7.2 A | ||||
— up to 400 V for current peak value n=20 rated value | 7.2 A | ||||
— up to 500 V for current peak value n=20 rated value | 7.2 A | ||||
— up to 690 V for current peak value n=20 rated value | 6.7 A | ||||
● at AC-6a | |||||
— up to 230 V for current peak value n=30 rated value | 4.8 A | ||||
— up to 400 V for current peak value n=30 rated value | 4.8 A | ||||
— up to 500 V for current peak value n=30 rated value | 4.8 A | ||||
— up to 690 V for current peak value n=30 rated value | 4.8 A | ||||
Minimum cross-section in main circuit at maximum AC-1 rated value | 4 mm² | ||||
Operational current for approx. 200000 operating cycles at AC-4 | |||||
● at 400 V rated value | 4.1 A | ||||
● at 690 V rated value | 3.3 A | ||||
Operational current | |||||
● at 1 current path at DC-1 | |||||
— at 24 V rated value | 20 A | ||||
— at 60 V rated value | 20 A | ||||
— at 110 V rated value | 2.1 A | ||||
— at 220 V rated value | 0.8 A | ||||
— at 440 V rated value | 0.6 A | ||||
— at 600 V rated value | 0.6 A | ||||
● with 2 current paths in series at DC-1 | |||||
— at 24 V rated value | 20 A | ||||
— at 60 V rated value | 20 A | ||||
— at 110 V rated value | 12 A | ||||
— at 220 V rated value | 1.6 A | ||||
— at 440 V rated value | 0.8 A | ||||
— at 600 V rated value | 0.7 A | ||||
● with 3 current paths in series at DC-1 | |||||
— at 24 V rated value | 20 A | ||||
— at 60 V rated value | 20 A | ||||
— at 110 V rated value | 20 A | ||||
— at 220 V rated value | 20 A | ||||
— at 440 V rated value | 1.3 A | ||||
— at 600 V rated value | 1 A | ||||
● at 1 current path at DC-3 at DC-5 | |||||
— at 24 V rated value | 20 A | ||||
— at 60 V rated value | 0.5 A | ||||
— at 110 V rated value | 0.15 A | ||||
● with 2 current paths in series at DC-3 at DC-5 | |||||
— at 24 V rated value | 20 A | ||||
— at 60 V rated value | 5 A | ||||
— at 110 V rated value | 0.35 A | ||||
● with 3 current paths in series at DC-3 at DC-5 | |||||
— at 24 V rated value | 20 A | ||||
— at 60 V rated value | 20 A | ||||
— at 110 V rated value | 20 A | ||||
— at 220 V rated value | 1.5 A | ||||
— at 440 V rated value | 0.2 A | ||||
— at 600 V rated value | 0.2 A | ||||
Operating power | |||||
● at AC-2 at 400 V rated value | 5.5 kW | ||||
● at AC-3 | |||||
— at 230 V rated value | 3 kW | ||||
— at 400 V rated value | 5.5 kW | ||||
— at 500 V rated value | 5.5 kW | ||||
— at 690 V rated value | 5.5 kW | ||||
● at AC-3e | |||||
— at 230 V rated value | 3 kW | ||||
— at 400 V rated value | 5.5 kW | ||||
— at 500 V rated value | 5.5 kW | ||||
— at 690 V rated value | 5.5 kW | ||||
Operating power for approx. 200000 operating cycles at AC-4 | |||||
● at 400 V rated value | 2 kW | ||||
● at 690 V rated value | 2.5 kW | ||||
Operating apparent power at AC-6a | |||||
● up to 230 V for current peak value n=20 rated value | 2.8 kVA | ||||
● up to 400 V for current peak value n=20 rated value | 4.9 kVA | ||||
● up to 500 V for current peak value n=20 rated value | 6.2 kVA | ||||
● up to 690 V for current peak value n=20 rated value | 8 kVA | ||||
Operating apparent power at AC-6a | |||||
● up to 230 V for current peak value n=30 rated value | 1.9 kVA | ||||
● up to 400 V for current peak value n=30 rated value | 3.3 kVA | ||||
● up to 500 V for current peak value n=30 rated value | 4.1 kVA | ||||
● up to 690 V for current peak value n=30 rated value | 5.7 kVA | ||||
Short-time withstand current in cold operating state up to 40 °C | |||||
● limited to 1 s switching at zero current maximum | 200 A; Use minimum cross-section acc. to AC-1 rated value | ||||
● limited to 5 s switching at zero current maximum | 123 A; Use minimum cross-section acc. to AC-1 rated value | ||||
● limited to 10 s switching at zero current maximum | 96 A; Use minimum cross-section acc. to AC-1 rated value | ||||
● limited to 30 s switching at zero current maximum | 74 A; Use minimum cross-section acc. to AC-1 rated value | ||||
● limited to 60 s switching at zero current maximum | 61 A; Use minimum cross-section acc. to AC-1 rated value | ||||
No-load switching frequency | |||||
● at AC | 10 000 1/h | ||||
Operating frequency | |||||
● at AC-1 maximum | 1 000 1/h | ||||
● at AC-2 maximum | 750 1/h | ||||
● at AC-3 maximum | 750 1/h | ||||
● at AC-3e maximum | 750 1/h | ||||
● at AC-4 maximum | 250 1/h | ||||
Control circuit/ Control | |||||
Type of voltage of the control supply voltage | AC | ||||
Control supply voltage at AC | |||||
● at 50 Hz rated value | 208 V | ||||
● at 60 Hz rated value | 208 V | ||||
Operating range factor control supply voltage rated value of magnet coil at AC | |||||
● at 50 Hz | 0.8 … 1.1 | ||||
● at 60 Hz | 0.85 … 1.1 | ||||
Apparent pick-up power of magnet coil at AC | |||||
● at 50 Hz | 37 VA | ||||
● at 60 Hz | 33 VA | ||||
Inductive power factor with closing power of the coil | |||||
● at 50 Hz | 0.8 | ||||
● at 60 Hz | 0.75 | ||||
Apparent holding power of magnet coil at AC | |||||
● at 50 Hz | 5.7 VA | ||||
● at 60 Hz | 4.4 VA | ||||
Inductive power factor with the holding power of the coil | |||||
● at 50 Hz | 0.25 | ||||
● at 60 Hz | 0.25 | ||||
Closing delay | |||||
● at AC | 9 … 35 ms | ||||
Opening delay | |||||
● at AC | 4 … 15 ms | ||||
Arcing time | 10 … 15 ms | ||||
Control version of the switch operating mechanism | Standard A1 – A2 | ||||
Auxiliary circuit | |||||
Number of NO contacts for auxiliary contacts instantaneous contact | 1 | ||||
Operational current at AC-12 maximum | 10 A | ||||
Operational current at AC-15 | |||||
● at 230 V rated value | 10 A | ||||
● at 400 V rated value | 3 A | ||||
● at 500 V rated value | 2 A | ||||
● at 690 V rated value | 1 A | ||||
Operational current at DC-12 | |||||
● at 24 V rated value | 10 A | ||||
● at 48 V rated value | 6 A | ||||
● at 60 V rated value | 6 A | ||||
● at 11
Xem thêm tại Datasheet Để được tư vấn trực tiếp, quý khách vui lòng liên hệ với chúng tôi theo thông tin sau: Cảm ơn quý khách đã truy cập vào website MTEE.VN. Kính chúc quý khách nhận được những thông tin hữu ích và có những trải nghiệm tuyệt vời trên trang. Thông tin bổ sung
Đánh giá (0) |
CAM KẾT CỦA CHÚNG TÔI
Cam kết chính hãng
Hoàn tiền 200% nếu phát hiện hàng giả, hàng nhái.
Cam kết tư vấn đúng
Chuyên gia tư vấn trực tiếp qua hotline/zalo: 0904.777.528
Cam kết bảo mật
Tuyệt đối không chia sẻ thông tin khách hàng cho bên thứ 3.
3RT2017-1AM21 – Contactor Siemens
1,047,000₫ Giá gốc là: 1,047,000₫.563,000₫Giá hiện tại là: 563,000₫.
Lưu ý: Giá bán hiện tại có thể khác so với giá hiển thị trên website, vui lòng liên hệ hoặc YÊU CẦU BÁO GIÁ bên dưới để nhận được mức giá ưu đãi nhất
➡ Mã sản phẩm: 3RT2017-1AM21 – Contactor Siemens
➡ Thông số kỹ thuật: power contactor, AC-3e/AC-3, 12 A, 5.5 kW / 400 V, 3-pole, 208 V AC, 50/60 Hz, auxiliary contacts: 1 NO, screw terminal, size: S00
Đặt mua sản phẩm tại MTEE.vn ngay để nhận được các ưu đãi hấp dẫn nhất chưa từng có
- Miễn phí giao hàng cho đơn hàng từ 5.000.000 VNĐ tới mọi tỉnh thành
- Miễn phí ship nội thành trong bán kính 5km với đơn hàng từ 500.000 VNĐ
- Quà tặng hấp dẫn lên tới 2.000.000 VNĐ
- Bảo hành chính hãng 12 tháng
Ngoài ra chúng tôi còn cung cấp các dịch vụ như:
- Lắp đặt và lập trình theo yêu cầu
- Tư vấn và hỗ trợ kỹ thuật trọn đời
Sản phẩm tương tự
Bộ nguồn Siemens
Bộ nguồn Siemens
Bộ nguồn Siemens
Bộ nguồn Siemens
Bộ nguồn Siemens
Bộ nguồn Siemens
Bộ nguồn Siemens
Thiết bị AS khác
Hỗ trợ 24/7
Hỗ trợ khách hàng mọi ngày trong tuần, bất cứ lúc nào
Chính sách chất lượng
Hoàn 100% tiền nếu sản phẩm không đạt tiêu chuẩn
Quan điểm kinh doanh
Khách hàng quyết định sự tồn tại và phát triển của công ty
Đánh giá 3RT2017-1AM21 – Contactor Siemens